Sag alarm settings, Configuring setpoints by using the display module – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 133

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

133

Setpoint Programming and Operation Chapter 5

Example 3 – Sag alarm. To set an alarm flag on a sag condition so that
RSEnergyMetrix software can log it and take action, use the following
settings.

Nominal system voltage is the nominal line to neutral voltage in Wye
and single-phase systems and nominal line to line voltage in Delta
systems. In 1404-M6 and 1404-M8 units, the high and low limits would
be the same as those found in setpoint 19, the built-in sag setpoint.
Setpoint release delay of 90 seconds sets alarm flag 3 long enough
that RSEnergyMetrix software can reliably log the alarm with a
one-minute log rate. Alarm flag 3 is selected because alarm flags 1 and
2 are tied to physical relay and KYZ outputs.

Configuring Setpoints by Using the Display Module

You may configure setpoint operations by navigating through the
PROG > PASS? > CONFIGURATION > SETPOINT menus, selecting a
setpoint number and programming the appropriate parameters.

Setpoint action delay

0 second (M4, M5)
0 tenths of a second (M6, M8)

Setpoint release delay

0 seconds (M4, M5)
0 tenths of a second (M6, M8)

Setpoint action type

1 - Energize relay 1 and set alarm flag 1

Sag Alarm Settings

Parameter

Suggested Value

Setpoint number

3

Setpoint type

1 - Voltage

Setpoint evaluation condition

2 - Under forward

Setpoint high limit

110% of nominal system voltage

Setpoint low limit

110% of nominal system voltage

Setpoint action delay

0

Setpoint release delay

90 seconds

Setpoint action type

3 - Set alarm flag 3

Phase Reversal Relay Settings

Parameter

Value