Controllogix tags used, E controllogix tags used – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 315

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

315

Sample Applications Appendix C

You must enter data into the Default and Custom tags.

Refer to User-configured Data Table on page 121

for the structure and

rules for the

User-configured Table Setup

data table and its default

settings.

See Parameters for Trend Log and Configurable Table Parameters on
page 268

for parameters that may be included in the User Configured

Table Setup.

ControlLogix Tags Used

Tag Name

Type

# of
Elems

Description

Table #

msgReadOld

MESSAGE

N/A

Read Existing Config

N30

msgWriteNew

MESSAGE

N/A

Write New Config.

N30

msgGetStatus

MESSAGE

N/A

Write Status

N32

Start

BOOL

1

Start Operation

Failed

BOOL

1

Failure Flag

Success

BOOL

1

Success Flag

Oneshot_1

BOOL

1

One shot

Oneshot_2

BOOL

1

One shot

Timer1

TIMER

1

Inter-message Delay

Timer2

TIMER

1

PM3000 Reset Time

Counter1

COUNTER

1

Message Retry

Default

INT

26

Default Configuration

Custom

INT

26

Custom Configuration

Old

INT

26

Previous Config

Download

INT

26

New Config to Write

Pwd

INT

1

PM3000 Password

Status

INT

2

Write Status

Select

INT

1

User Selection

IMPORTANT

Words 0…3 of the User Configurable Table Setup array must have
specific values.

Word 0: power monitor password (default = 0)

Word 1 must be one of the following decimal values:

31, for CSP/PCCC

1 or 37 for CIP

Word 2: zero (0) for writes to table 31. For configuring instance 1:
0 = all integer or data type, 1 = float data type.

Word 3: between 1 and 295 incl.