Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 197

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

197

Powermonitor 3000 Data Tables Appendix A

14

40215

Restore factory default
config

0…1

-

0

0 = No action 1 = Restore factory default settings

15

40216

Clear status input counters

0…3

-

0

0 = No action
1 = Clear counter #1

2 = Clear counter #2
3 = Clear both

16

40217

Wdog action

0…1

-

1

0 = Restart, log an event and halt operation
1 = Restart, log an event and resume

Refer to Watchdog Timeout Action on page 55

17

40218

Force relay output

0…3

-

0

0 = No change
1 = Force energize the relay
2 = Force de-energize the relay
3 = Release force of relay output
Overrides setpoint or pulse output control

18

40219

Force solid-state KYZ output 0…3

-

0

19

40220

Default relay state in event
of communication loss

0…3

-

0

0 = Last state / resume
1 = Last state / freeze
2 = De-energize / resume
3 = De-energize / freeze

Refer to Communication Loss Behavior on
page 140

20

40221

Default KYZ state in event
of communication loss

21

40222

DM text scroll rate

0…1

-

1

0 = Slow; 1 = Fast

22

40223

Energy counter rollover

4…15

Digits 15

Refer to Configurable Energy Counter Rollover
on page 35

23

40224

Forced demand sync delay

0…900

s

10

0 = Disable, 1…900 = number of seconds delay

24

40225

Reserved

0

-

0

Reserved. Must be 0 on a write, returns 0

25

40226

Reserved

0

-

0

Reserved. Must be 0 on a write, returns 0

Advanced Device Configuration

Element
No.

Modbus
Address

Element name

Range

Units Default

Value

Comment