User-configured table setup parameters, User-configured table setup, Table – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 233

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

233

Powermonitor 3000 Data Tables Appendix A

User-configured Table Setup Parameters

CSP File No.

N30

Remote I/O BT

35

CIP Assy. Inst.

35 (Write), 36 (Read)

No. of Elements

26

User Configurable No

Data Type

Integer

Data Access

Read /Write

PM3000 Type

All

Applies to

User-configured Table Results Parameters on

page 235

User-configured Table Setup

Element
No.

Modbus
Address

Element Name

Range

Default

Value

Comment

0

41101

Password

0…9999

0

Required for configuration, returns -1

1

41102

DF1 or Ethernet (CSP) File No.

31

31

Refer to User-configured Data Table on page 121

RIO BT No.

62

62

DeviceNet, EtherNet/IP, or
ControlNet Ass’y Inst.

1, 37

37

Modbus

1000

31

2

41103

DeviceNet, EtherNet/IP, or
ControlNet instance 1 data type

0…1

0

3

41104

Selection for parameter #1

0…301

71 (L1-L2 V)

4

41105

Selection for parameter #2

72 (L2-L3 V)

5

41106

Selection for parameter #3

73 (L3-L1 V)

6

41107

Selection for parameter #4

63 (I1)

7

41108

Selection for parameter #5

64 (I2)

8

41109

Selection for parameter #6

65 (I3)

9

41110

Selection for parameter #7

90 (W)

10

41111

Selection for parameter #8

98 (VA)

11

41112

Selection for parameter #9

94 (VAR)

12

41113

Selection for parameter #10

111 (PF)

13

41114

Selection for parameter #11

100 (Dmd W)

14

41115

Selection for parameter #12

122 (kWh)

15

41116

Selection for parameter #13

130 (Status)

16

41117

Selection for parameter #14

14 (Year)