164

Publication 1404-UM001F-EN-P - November 2009

Chapter 8 Advanced Features

Each data point is expressed in calibrated analog-to-digital (A/D)
converter counts with a resolution of 8192 (13-bit w/sign) or 128 (7-bit
w/sign). A client may calculate the primary-side instantaneous voltage
or current magnitude of each data point by using the following
formula:

Where:

M

i

= instantaneous value of the voltage or current data point

M

(max rms)

= max rms magnitude

= 399.0 line-to-neutral volts for channels 1, 3, and 5
= 691.1 line-to-line volts for channels 1, 3, and 5
= 10.6 amperes for channels 2, 4, 6, and 7

R

max

= maximum resolution

= 8192 for 13-bit w/sign, capture types 0, 1, and 2
= 128 for 7-bit w/sign, capture types 3, 4, and 5

N

t

= PT or CT ratio

= PT or CT primary / PT or CT secondary

M

data

= value of the data point from the

Oscillograph

Configuration/Read-back Data Select

table

For example, consider the following capture:

PT primary = 13.8 kV

PT secondary = 120 V

CT primary = 100 A

CT secondary = 5 A

Delta voltage mode (line-to-line)

Capture type = 2

You would multiply each data point by the following factor to
correctly display the waveform:

M

i

M

max rms

(

)

2

R

max

-------------------------------------- N

t

M

data

=

Factor

691.1 1.414

(

)

8192

13800

120

(

)

13.72

=

=