Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 111

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

111

Communication Chapter 4

7. Select 3 as the Configuration instance and leave its Size set to 0

bytes and click the Next.

8. Set the Requested Packet Interval to 100 ms or greater.

The power monitor does not respond reliably to an RPI of less
than 100 ms.

Requested Packet Interval Setup

The power monitor data is found in controller tags.

Power Monitor I/O Tags