Communication Chapter 4

Optional RS-232 Communication

Powermonitor 3000 units with a catalog number ending in -232 are
equipped with an optional RS-232 serial port in addition to the native
port. These units are set up at the factory to auto-sense the protocol
used by the initiator or master device on the network. The
configuration parameters are the same as the native RS-485 port with
the following exception:

Flow Control: Enables or disables hardware handshaking.
Default disabled

Native Communication Configuration Summary

Parameter Description

Range Default

User
Setting

Protocol DF1

Full-duplex
DF1
Half-duplex
Slave
Modbus RTU
Slave
Auto-Sense

Auto-Sense

Delay

Time between receiving
a request and
transmitting a response

0…75 ms

10 ms

Communication
Rate

RS-485 port
communication bit rate

1.2 Kbps
2.4 Kbps
4.8 Kbps
9.6 Kbps
19.2 Kbps
38.4 Kbps
57.6 Kbps

9600 baud

RS-485 Address

Uniquely identifies the
Powermonitor device on
a multi-drop network

1…247

Unit ID number

Data Format

Data bits / Stop bits /
Parity

8 / 1/ none
8 / 1/ even
8 / 1/ odd

8 / 1 / none

Inter-Character
Timeout

Mimimum delay
between characters that
indicates end of Modbus
message packet

0…6553 ms

0 (= 3.5
character times)

Error Checking

BCC, CRC

CRC