Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 113
Publication 1404-UM001F-EN-P - November 2009
113
Communication Chapter 4
3. Add the power monitor as a Generic ControlNet module.
Typical ControlNet Configuration
4. Select Data-INT as the Communication Format.
5. Enter the ControlNet address of the power monitor.
6. Set the Connection Parameters as shown for the default
configuration.
If you change the configuration of the input assembly instance,
enter its new size in Instance 1 here.
7. Select 3 as the Configuration instance and leave its Size set to 0
bytes and click Next.
8. Set the Requested Packet Interval to a binary multiple of the
network update time (NUT) greater than 100 ms.
The power monitor update rate is typically 100 ms.
Requested Packet
The power monitor data is found in controller tags.