Setpoint types – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 129

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

129

Setpoint Programming and Operation Chapter 5

Setpoint Low Limit

The value being used as a reference to
deactivate the setpoint for over comparisons,
or to activate the setpoint for under
comparisons.

0…10,000,000

Depends on type

0

Setpoint Action Delay The minimum time in seconds that the

setpoint limit must be exceeded continuously
before the setpoint will trigger.

0…3600

Sec (M4, M5)

0

0…30,000

0.1 Sec (M6, M8)

Setpoint Release
Delay

The minimum time in seconds that the
setpoint limit must not be exceeded
continuously before the setpoint releases.

0…3600

Sec (M4, M5)

0

0…30,000

0.1 Sec (M6, M8)

Setpoint Action Type

The action that occurs when the setpoint is
triggered.

0…32 (see details in the
Setpoint Action Type table on

page 131

)

0

Clear Accumulated
Time

Clear the time accumulator for this setpoint

Yes
No

N/A

Setpoint Configuration

Parameter Name

Parameter Description

Range

Units

Default

Setpoint Types

Setpoint Type

Description

Units

M4,
M5

M6

M8

0

Not used

-

1

Voltage

(1)

Volts

2

Current

(1)

Amps

3

Voltage unbalance

Percent

4

Current unbalance

5

Neutral current

Amps

6

W

Watts

7

VAR

VARs

8

VA

VA

9

Total true PF

Percent

10

Total disp PF

11

Total dist PF

12

W demand

Watts

13

VAR demand

VARs

14

VA demand

VA

15

Amp demand

Amps

16

Projected amp demand

Amps

17

Projected W Demand

Watts

18

Projected VAR Demand

VARs

19

Projected VA Demand

VA

20

Frequency

Hz

21

Phase rotation

-

22

Crest factor voltage

Volts

23

Crest factor current

Amps