Data files, Slc 500 sequencer operation – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 308

Advertising
background image

308

Publication 1404-UM001F-EN-P - November 2009

Appendix C Sample Applications

SLC 500 Sequencer Operation

This example uses a sequencer instruction and indirect addressing to
optimize program operation.

During initialization of Run mode, the sequencer input file is loaded
with the numbers corresponding to the two explicit message transfers
to be performed. Once Run mode has begun, the ladder program
remains in this mode.

Data Files Used

TIP

The speed at which the processor performs the messages may be
altered by resetting the On-Delay timer that is located within the
sequencer output rung. However, the availability of new data values
is controlled by the power monitor table update rate.

Data Files

Data File
Address

Number of
Elements

Description

N9

1

N9:0 Sequencer Output

N10

Variable

N10:0 Sequencer Input

R6:0

Sequencer Control

Message Read Data Table Locations

(Control/Data)

N20 / F30

14

Voltage/Current Data

N21 / F31

13

Real-Time Power

N22 / F32

13

Power Factor

N23 / N33

23

kWh and kVAh

N24 / N34

23

kVarh

N25 / F35

10

Demand

N26 / N36

27

Diagnostic