Harmonic Results; THD, Crest Factor, and More Parameters

CSP File No.

F34

Remote I/O BT

23

CIP Assy. Inst.

41

No. of Elements

9 (M4, M5); 10 (M6, M8)

User Configurable No

Data Type

Floating Point

Data Access

Read only

PM3000 Type

See table

Harmonic Results; THD, Crest Factor, and More

Element
No.

Modbus
Address

M4
M5

M
6

M
8

Element Name

Range

Comment

0

31201-02

• •

Channel number

1…9

Refer to Reading Harmonic Analysis Data on page 172

1

31203-04

• •

% IEEE THD

0.0…1000.0

2

31205-06

• •

% IEC thd (DIN)

0.0…1000.0

3

31207-08

• •

Crest Factor

0.0…10.0

4

31209-10

• •

THD & Crest iteration 0…32,767

5

31211-12

Reserved

0

• •

TIF

0.0…999.9x10

22

6

31213-14

Reserved

0

• •

K-Factor

0.0…999.9x10

22

7

31215-16

Reserved

0

• •

IEEE-519 TDD

0.0…999.9x10

22

8

31217-18

Reserved

0

• •

IEEE-519 Pass/Fail

-1…1

9

31219-20

Reserved

0

• •

FFT iteration

0…32,767