Publication 1404-UM001F-EN-P - November 2009

Chapter 3 Powermonitor 3000 Unit Operations

Display Module
Functionality

The display module is a simple terminal that allows you to easily view
metering parameters or change configuration items. The display
module uses three modes of operation.

Display mode allows you to view power monitor parameters
including metering, setpoint, min/max log, event log and
self-test information. You may also select a default screen to be
displayed at power-up or after 30 minutes without key activity.

Program mode allows you to change configuration parameters,
with security against unauthorized configuration changes. Each
power monitor is password protected. In Program mode, the
display module phase indicators (L1,L2,L3,N) flash.

Edit mode allows you to modify the selected parameters. In Edit
mode, the parameter being modified flashes, and the phase
indicators (L1,L2,L3,N) remain solid.

Energy and Demand Results

Parameter Description

Range

Units

Kilo-Watt Hours Forward

The total real power consumed

0…1.0x10

12

kWh

Kilo-Watt Hours Reverse

The total real power produced

Kilo-Watt Hours Net

The sum of forward and reverse power

Kilo-VAR Hours Forward

The total reactive power consumed

0…1.0x10

12

kVARh

Kilo-VAR Hours Reverse

The total reactive power produced

Kilo-VAR Hours Net

The sum of forward and reverse reactive power

Kilo-VA Hours Net

The total apparent power consumed

0…1.0x10

12

kVAh

Amp Hours Net

Accumulated amp-hours consumed

0…1.0x10

12

Ah

Demand Current

The calculated demand for average current

0…999.9x10

21

Amps

Max Demand Current

The maximum (peak) demand for current. (included in
Min/Max Log)

Demand Kilo-Watts

The calculated demand for real power

0…999.9x10

21

kW

Max Demand Kilo-Watts

The maximum (peak) demand for real power
(included in Min/Max Log)

Demand Kilo-VARs

The calculated demand for reactive power

0…999.9x10

21

kVAR

Max Demand Kilo-VARs

The maximum (peak) demand for reactive power
(included in Min/Max Log)

Demand Kilo-VA

The calculated demand for apparent power

0…999.9x10

21

kVA

Max Demand Kilo-VA

The maximum (peak) demand for apparent power
(included in Min/Max Log)

Projected Current Demand

(1)

The projected demand for average current

0…999.9x10

21

Amps

Projected Kilo-Watt Demand

(1)

The projected demand for real power

0…999.9x10

21

kW

Projected Kilo-VAR Demand

(1)

The projected demand for reactive power

0…999.9x10

21

kVARs

Projected Kilo-VA Demand

(1)

The projected demand for apparent power

0…999.9x10

21

kVA

(1)

Values returned depend on user selection of projected demand type in Advanced Configuration.