Simple demand management settings, Phase reversal relay settings – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 132

Advertising
background image

132

Publication 1404-UM001F-EN-P - November 2009

Chapter 5 Setpoint Programming and Operation

Example 1 – Simple demand management: To configure setpoint 1 to
energize output relay 1 when projected demand exceeds 100 kW for
more than one second and de-energize relay 1 when projected
demand falls below 90 kW for more than two seconds, you could use
the following settings.

Example 2 – Phase reversal relay: To use setpoint 2 to energize the
output relay as a permissive for starting a three-phase motor, you
could use the following settings.

ATTENTION

These examples are intended to demonstrate setpoint configuration
only. They should not be used as sample application programming
references. Carefully consider all control, operational and safety
issues when designing and implementing setpoint operations.

Simple Demand Management Settings

Parameter

Value

Setpoint number

1

Setpoint type

17 - Projected Watt Demand

Setpoint evaluation condition

0 - Over forward

Setpoint high limit

100,000 watts

Setpoint low limit

90,000 watts

Setpoint action delay

1 second (M4, M5)
10 tenths of a second (M6, M8)

Setpoint release delay

2 seconds (M4, M5)
20 tenths of a second (M6, M8)

Setpoint action type

1 - Energize relay 1 and set alarm flag 1

Phase Reversal Relay Settings

Parameter

Value

Setpoint number

2

Setpoint type

21 - Phase rotation

Setpoint evaluation condition

4 - Equal

Setpoint high limit

1 - ABC

Setpoint low limit

Not used