Controlnet communication option – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 112

Advertising
background image

112

Publication 1404-UM001F-EN-P - November 2009

Chapter 4 Communication

Powermonitor 3000 Web Access

You may view a number of data tables by simply pointing your web
browser to the IP address of your power monitor from a computer
with access to the unit’s subnet. Example:

http://192.1.1.207

.

On the left side of the web page is a list of data table that you may
view. Each list entry is a hyperlink that takes you to the selected table
with a single mouse click. Each table appears as a tabular display with
value descriptions and values. To return to the main page, click
Refresh on your browser.

Powermonitor 3000 Web Page

Additional Ethernet Information

The power monitor utilizes the following fixed Ethernet port numbers:

HTML: Port 80

CSP: Port 2222

CIP: Port 44818

Modbus TCP: TCP port 502

ControlNet Communication Option

Powermonitor 3000 ControlNet units support a Class 1 connection to
Instance 1 and 2.

1. To utilize this scheduled connection to a ControlLogix controller,

open the controller program offline in RSLogix 5000 software.

2. Select the ControlNet bridge module (1756-CNB or 1756-CNBR)

in the I/O configuration.