Parameter selection bitfield value – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 120

Advertising
background image

120

Publication 1404-UM001F-EN-P - November 2009

Chapter 4 Communication

How to Clear or Preset Energy Counters by Using Communication

You may clear or preset the energy counters by performing a table
write to the

Metering Real and Apparent Energy Results

table or the

Metering Reactive Energy and Amp-hour Results

table. These

read/write tables each contain 23 integer elements.

Password: required to clear or preset an energy counter, returns
-1

Parameter select: bitfield used to select parameter for clearing or
presetting

See below.

Energy counter values: expressed in integer-array format, see

page 82

Metering iteration: increments by 1 with each new set of results,
rolls to 0 at 32,767

The Parameter select bitfield value selects the parameter or parameters
to be cleared or preset during the current write, as shown in the table
below.

You may select the value at which the energy counters roll over to 0
in the

Advanced Device Configuration

table.

Parameter Selection Bitfield Value

Bitfield Value

Parameter

Binary

Decimal

Table 14

Table 15

000

0 -

-

001

1

kWh forward

kVARh forward

010

2

kWh reverse

kVARh reverse

100

4 kVAh

kAh

111

7

All

All