Harmonic Analysis

The power monitor provides harmonic data to help you understand
this important element of power quality in your facility. Each model
provides a different level of harmonic information.

The

Harmonic Analysis Functionality

table provides an overview of

the harmonic analysis available in each model. You may access all
harmonic data by using communication. The display module can
access average values of the parameters as indicated in the DM
column.

IEEE THD and DIN

Both of these total harmonic distortion calculation methods provide a
summary indication of the amount of distortion due to harmonics
present in a system. The standard IEEE definition of harmonic
distortion is Total Harmonic Distortion (THD) and is computed for
each channel as follows:

Harmonic Analysis Functionality

Harmonic data

DM
(Avg.)

M4
M5

M6

M8

Per
Current
Channel

Per
Voltage
Channel

Avg. Of
Current
Channels

Avg. Of
Voltage
Channels

IEEE Total Harmonic Distortion (THD)

IEC Distortion Index (DIN)

Crest Factor

Telephone Interference Factor (TIF)

K-factor

IEEE-519 Total Demand Distortion (TDD)

IEEE 519 Pass / Fail

Harmonic distortion, harmonics 1

41

Harmonic magnitude, harmonics 1

41

Harmonic distortion, harmonics 42

63

Harmonic magnitude, harmonics 42

63

THD

Σ

n

2

=

Hn

(

)

2

H1

-------------------------

=

Where:

H

n

= magnitude of the n

th

harmonic

(n

41 or 63)

H

1

= magnitude of fundamental