94

Publication 1404-UM001F-EN-P - November 2009

Chapter 4 Communication

The data table number of error request and element offset of error
request in the

Write Error Status

table is updated with the first Modbus

address of the table and element offset that the incoming request
packet attempts to write to.

If a client device requests too large a data size, the power monitor
returns the requested data padded with zeroes up to the requested
data size rather than returning an error.

When the

User-configured Table Setup

table is used together with

Modbus, the value for element 1 should be 1000.

The value for element 0 of the

Write Error Status

table is the first

Modbus address of data table written to last.

For function code 03, 04, and 16, the number of words of user data is
limited to 100. If it is over 100, exception code 3 will be returned to
the master and error code 3 occurs.

Modbus Error Codes

Error
Code

Description

Meaning

Response
Exception
Code

0

No error.

None

1

Function Code
cannot Broadcast.

The function does not support Broadcast.

Nothing
transmitted

2

Function Code not
supported.

The controller does not support this
Modbus function or sub-function.

1

3

Bad Command
Length

The Modbus Command is the wrong size.

3

4

Bad Length

The function attempted to read/write past
the end of a data file.

3

5

Bad Parameter

The function cannot be executed with
these parameters.

3

6

Bad Table
Number

The table number does not exist.

2

7

Bad Modbus
Address

The function attempted to access an
invalid Modbus address.

3

8

Table Write
Protected

The function attempted to write to a
read-only table.

3

9

Table Access
Denied

Access to this table is not granted.

2