Chapter 3 Powermonitor 3000 Unit Operations

Explanation of Power Factor Values

Energy Results

The power monitor calculates energy values including kWh forward,
reverse and net; kVAh; kVARh forward, reverse and net; and kAh. You
may read these values by using the display module or via
communication.

Phase 1 True Power Factor

The ratio between the power and apparent
power for an individual phase or all three
phases; signed to show lead (+) or lag (-).

-100…100 Percent

Phase 2 True Power Factor

Phase 3 True Power Factor

Total True Power Factor

Phase 1 Distortion Power Factor

The ratio between the magnitude of the
fundamental and the sum of the magnitudes for
all of the current harmonics for an individual
phase or all three phases.

0…100 Percent

Phase 2 Distortion Power Factor

Phase 3 Distortion Power Factor

Total Distortion Power Factor

Phase 1 Displacement Power Factor

The cosine of the phase angle between the
fundamental voltage and current for an
individual phase or all three phases; signed to
show lead (+) or lag (-).

-100…100 Percent

Phase 2 Displacement Power Factor

Phase 3 Displacement Power Factor

Total Displacement Power Factor

Power and Power Factor Results

Parameter Description

Range

Units

I

IV

II

III

90˚

270˚

180˚

Pf = 0
+kVAR (Import)
kVARHR-F (Forward)

Pf = 0
-kVAR (Export)
kVARHR-R (Reverse)

Pf = 100%
+kW (Import)
kWH-F (Forward)

Pf = 100%
-kW (Export)
kWH-R (Reverse)

(Power Factor
Lagging)
(-)

(Power Factor
Leading)
(+)

(Power Factor
Lagging)
(-)

(Power Factor
Leading)
(+)