Metering demand results parameters, Metering demand results – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 208

Advertising
background image

208

Publication 1404-UM001F-EN-P - November 2009

Appendix A Powermonitor 3000 Data Tables

Metering Demand Results Parameters

CSP File No.

F18

Remote I/O BT

25

CIP Assy. Inst.

17

No. of Elements

10

User Configurable No

Data Type

Floating point

Data Access

Read only

PM3000 Type

All

Metering Demand Results

Element
No.

Modbus
Address

Element name

Units

Range

Comment

0

30401-02

Demand Current

Amps (A)

0.0…999.9x10

21

Refer to Energy Results on page 34

.

1

30403-04

Demand Power

Watts (W) 0.0…999.9x10

21

2

30405-06

Demand Reactive Power

VAR

0.0…999.9x10

21

3

30407-08

Demand Apparent Power

VA

0.0…999.9x10

21

4

30409-10

Projected Demand I

Amps

0.0…999.9x10

21

Refer to Projected Demand Calculation on
page 36

.

5

30411-12

Projected Demand W

Watts

0.0…999.9x10

21

6

30413-14

Projected Demand VAR

VAR

0.0…999.9x10

21

7

30415-16

Projected Demand VA

VA

0.0…999.9x10

21

8

30417-18

Elapsed demand period time

Minutes

0.0…999.9x10

21

The time elapsed within the current demand
period.

9

30419-20

Metering iteration

-

0…32,767

Increments by 1…32,767, rolls over to 0.

Advertising