Metering update rate, Min and max metering update rate for each model – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 60

Advertising
background image

60

Publication 1404-UM001F-EN-P - November 2009

Chapter 3 Powermonitor 3000 Unit Operations

Metering Update Rate

The metering update rate is a measure of how often the power
monitor calculates new metering results. The metering update rate is
not significant in most applications, but can be important in some
control applications. The metering update rate affects how quickly a
setpoint can respond to an electrical event and affects how often new
metering results are available for communication. The metering
update rate is dependent on the power monitor model and device
configuration.

The table below contains information that can be used to calculate the
metering update rate for a specific model containing specific
configuration selections.

This table lists the minimum and maximum possible metering update
rate for each model based on information from the Metering Update
Rate Calculation table.

Metering Update Rate Calculation Based on Model and Device Configuration

Model and Config Options

M4

M5 M6

M8 Update Rate

Base metering update rate

50 ms

If device is an M4

Add 10 ms

If RMS Resolution = High (see the

Advanced

Device Configuration

table)

Add 10 ms

If catalog # contains ENT, CNT, or DNT

Add 5 ms

If the Min/Max log is enabled (see the

Min/Max

Log Configuration/Read-back Select

table)

Add 5 ms

If more than 5 setpoints are configured

Add 5 ms

If Oscillography is enabled (see the

Oscillograph

Configuration/Read-back Data Select

table)

Add 5 ms

If Transient detection is enabled (see the

Transient Analysis Configuration/Read-back
Select

table)

Add 15 ms

If Meter Result Set is set to Tranducer mode or
Emergy Meter Mode (see the

Advanced

Metering Configuration

table)

Subtract 5 ms

Min and Max Metering Update Rate for Each Model

Model

Min and Max
Metering Update
Rate

M4

60

85 ms

M5

50

75 ms

M6

50

80 ms

M8

45

95 ms

Advertising