Basic device configuration – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 48

Advertising
background image

48

Publication 1404-UM001F-EN-P - November 2009

Chapter 3 Powermonitor 3000 Unit Operations

Refer to the Device Configurations Summary table on

page 50

for a

summary of basic and advanced device configuration settings. You
may use a copy of this table to record your configuration settings.

Basic Device Configuration

The basic unit configuration sets the wiring mode, PT ratios and CT
ratios to match your power system. Every power monitor requires
basic configuration. To perform basic configuration by using the
display module, navigate through these menus: PROG. > PASS? >
CONFIGURATION > BASIC. You may also set the basic device
configuration via communication by writing to the

Basic Device

Configuration Parameters

table.

Wiring Mode

Select the wiring mode to match the physical configuration of your
power system.

Your wiring mode choice must match the wiring diagrams found in
the Powermonitor 3000 Unit Installation Instructions, publication
1404-IN007, for proper operation and accuracy.

Your choices include the following:

Delta 3 CT

Delta 2 CT

Direct Delta 3 CT

Direct Delta 2 CT

Open Delta 3 CT

Open Delta 2 CT

Wye (default)

Single Phase

Demo

You may choose Demo mode for training or demonstration purposes.
In Demo mode, the power monitor returns internally generated
results.