Input and output ratings, Control relay, Relay life – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 338: General input, output, and environmental ratings

Advertising
background image

338

Publication 1404-UM001F-EN-P - November 2009

Appendix D Technical Specifications

General Input, Output, and Environmental Ratings

Input and Output Ratings

Control Power

1404-xxxxA-xxx

102…264V ac 47…63 Hz or
106…275V dc
(0.2 A max loading)

1404-xxxxB-xxx

18…50V dc (15V A max loading)

Voltage Sense
Inputs: V1, V2, V3

Input Impedance: 1 Mohm min, 399V ac max; V1, V2 and V3 to N.

Current Sense
Inputs: I1, I2, I3, I4

Overload Withstand:
15 A Continuous,
200 A for 1 s
Burden: 0.05V A
Impedance: 0.002 ohms
Maximum Crest Factor at 5 A is 3
Starting Current: 5 mA

Status Inputs

Contact Closure (Internal 24V dc)

Control Relay
KYZ Output

(1) ANSI C37.90-1989 trip duty
(1) Solid State KYZ - 80 mA at 240…300V dc

Control Relay

(1)

(1)

Meets ANSI/IEEE C37.90-1989 standards for trip duty.

Rating

50/60 Hz ac rms

DC

Max Resistive Load Switching

10 A at 250V
(2500V A)

10A at 30V and 0.25A at
250V

Min Load Switching

10 mA at 24V

10 mA at 24V

UL 508, CSA 22.2, IEC Rating
Class

B300

Q300

Max Make Values (Inductive
Load)

30 A at 120V
15 A at 240V
(3600V A)

0.55 A at 125V
0.27 A at 250V
(69V A)

Max Break Values (Inductive
Load)

3 A at 120V
1.5 A at 240V
(360V A)

0.55A at 125V
0.27 A at 250V
(69V A)

Max Motor Load Switching

1/3 HP at 125V
1/2 HP at 250V

Relay Life

(1)

(1)

Meets ANSI/IEEE C37.90-1989 standards for trip duty.

Parameter

Number of Operations

Mechanical

5 X 10

6

Electrical

1 X 10

5

Advertising