Oscillograph configuration/read-back data select, Oscillograph, Configuration/read-back data select – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 243: This read/write, Tabl

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

243

Powermonitor 3000 Data Tables Appendix A

Oscillograph Configuration/Read-back Data Select Parameters

CSP File No.

N39

Remote I/O BT

15

CIP Assy. Inst.

46 (Write), 47 (Read)

No. of Elements

11

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

M6, M8 only

Applies to:

Oscillograph Results Parameters

Oscillograph Configuration/Read-back Data Select

Element
No.

Modbus
Address

Element Name

Range

Default
Value

Comment

0

-

Password

0…9999

0

Required for configuration, -1 for readback
select, returns -1

1

-

Capture No.

0…8 (M6)
0…2 (M8)

1

Refer to Configuring Oscillography on page 160

2

-

Channel No.

1…7

1

3

-

Block No.

See

page 161

1

4

-

Read-back mode

0…2

0

5

-

Clear/trigger command

0…10

0

6

-

Capture type

-1…5

0

7

-

% Pre-trigger

0…100

90

8

-

Reserved

0

0

9

-

Capture clear status

0…255

-

10

-

Capture ready status

0…255

-