Powermonitor 3000 Data Tables Appendix A

Optional Communication Configuration Parameters

CSP File No.

N14

Remote I/O BT

24

CIP Assy. Inst.

12 (Write), 13 (Read)

No. of Elements

20

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

TIP

Select the table that applies to your Powermontior 3000 unit.

Ethernet

Element
No.

Modbus
Address

Element name

Range

Units

Default

Value

Comment

0

40401

Password

0…9999

-

0

Valid password required to change
configuration data. Returns -1

1

40402

IP address byte a

0…255

-

192

Format: aaa.bbb.ccc.ddd. Static IP address
of this device (for example 130.151.32.86).
If connected to a network, IP address must
be unique. (255.255.255.255 is not
permitted.)

2

40403

IP address byte b

168

3

40404

IP address byte c

254

4

40405

IP address byte d

Device ID Factory-assigned device ID

5

40406

Subnet mask byte a

0…255

-

255

Format aaa.bbb.ccc.ddd.

6

40407

Subnet mask byte b

255

7

40408

Subnet mask byte c

0

8

40409

Subnet mask byte d

0

9

40410

Gateway IP address byte a

0…255

-

128

IP address of the gateway on this subnet
used to route messages to other subnets
(wide area networking).

10

40411

Gateway IP address byte b

1

11

40412

Gateway IP address byte c

1

12

40413

Gateway IP address byte d

1

13

40414

Protocol selection

(1)

0…2

-

0

0 = CIP, 1 = CSP, 2 = CIP/CSP

14

40415

Reserved

0

-

0

Reserved. Must be 0 on a write, returns 0

15

40416

16

40417

17

40418

18

40419

19

40420

(1)

Master module version 4 or later, Ethernet firmware version 3 or later.