Data Logging Chapter 7

Only mode 0, 1, and 2 are supported by DF1 and remote I/O
communication. In modes 0, 1, and 2 the client need only read the
results table repeatedly until the entire Trend Log is read. In modes
3…6 the client must alternate writes to select the next read-back
record with reads of the results table.

You may obtain the number of records in the Trend Log by reading
the

Trend Log Configuration/Read-back Record Select

table, elements

7 and 8.

The number of records is (element 7) * 1000 + (element 8).

Only the following elements are needed during a record-selection
write:

Password: -1

DeviceNet unique write identifier: as applicable

Reserved words: must be 0

Read-back mode: see above

The

Trend Log Results

table is a read-only table of 14 (DeviceNet

network) or 22 (all other communication options) floating-point
elements as follows:

Reserved element: returns 0

Internal identifier: increments by 1 to 15 for each trend log
record then rolls over to 0

Time stamp: in 4-element timestamp format. See

page 55

.

User-selected parameters: parameters you selected when you
configured the Trend Log.

Min/Max Log

The Min/max Log maintains a time-stamped record of the minimum
and maximum values of up to 74 metering parameters. You can
monitor values over a day, a week, a month or any period to record
the highest and lowest values of voltage, current, or power factor.

Most industrial utility bills include a charge based on the maximum
demand recorded during the billing period. You could use the
Min/max log to provide that piece of data for generating an internal or
shadow billing report.