Publication 1746-6.1.2 - July 2000

Setting Up Your SLC Servo Module 7-31

System Parameters

Use the system parameters in the following table to define your
system-related specifications.

Speed/Direction of
Move Off the Limit
Switch

M0:s.18,19

This parameter is used during all homing
operations except Homing Without a Limit
Switch or Marker.

Speed/Direction of
Move to the Marker

M0:s.20,21

This parameter is used during all homing
operations except Homing Without a Limit
Switch or Marker.

Home Tolerance

M0:s.36,37

Specifies the position band around the home
position.

Name

Location

Description

Name

Location

Description

Enable Incremental
Position Command

M0:s.0/13

This bit enables incremental position command
in the command mode (i.e., words 2 and 3).
Refer to

Understanding Discrete Block Commands

from the SLC processor in this chapter.

Blend Move Profile

M0:s.0/14

When set, this bit redefines the mapping of all
configuration parameters to specify a blend
profile. Refer to

Blend Profile information in this

chapter.

Mode Flag

M0:s.0/15

• If this bit is set, the SLC Servo Module interprets

the incoming data as configuration information.
The configuration is allowed if there is no motion
in progress and the system is in the Estop.

• If this bit is clear, M-file contents are ignored

because M-files are only used for SLC Servo
Module configuration with this release.

Discrete Bit Status
Word 0 Definition

M0:s.1/7,M0:s1/6

Specifies the content of Discrete Bit Status
Word 0 being sent from the SLC Servo Module
to the SLC processor.

Inhibit Informational
Codes

M0:s.1/8

This bit, when set, inhibits (i.e., forces
informational code sent to SLC to 0) the
reporting of all informational codes in the SLC
Servo Module to SLC processor Discrete
Control Status.

Inhibit Minor Fault
Code

M0:s.1/9

This bit, when set, inhibits (i.e., forces minor
fault code sent to SLC to 0) the reporting of all
minor fault codes in the SLC Servo Module to
SLC processor Discrete Control Status. When
clear, all minor faults detected by the SLC Servo
Module are reported to the SLC processor. You
must clear them using either the Clear Fault or
Clear All Faults bit.