Chapter

9

Programming System Variables

Overview

This chapter provides information to help you program the module
for the command mode of operation. This chapter includes the
following topics:

Using position initialization commands

Using online configuration commands

Understanding status information

Understanding SLC Servo Module processor status

Using Position Initialization
Commands

The initialization commands that are discrete block commands from
the SLC Processor are:

Home axis

Set home

Set retract position

Preset position

Using the Home Axis Command

When you execute the Home Axis command, the following conditions
must exist before the homing operation can begin:

The motion control system must be out of Estop.

There must be no motion in progress.

If the system is in Estop, an error is sent to the SLC processor. If there
is motion in progress, that motion is canceled. Home axis parameters
for word 5, bit 0 appear in the table below.

1

s = Slot number for the SLC Servo Module.

Block Command Parameters

Location

1

Format

Possible Values

Default

Bit Specifications

O:s.4

Bits

0000 0000 0000 0000

0

Home Axis

O:s.5

Bits

0000 0000 0000 0001

0

% Acceleration Ramp

O:s.6-O:s.7

Float

0.0 to 1.0

1.0

Speed Direction to Start Homing Axis

O:s.8-O:s.9

Float

–physical limit to +physical limit 0.0