10-6 Troubleshooting

Figure 10.6 Data table for File N31

The above configuration is for a SPEED move at 100% accel/decel at 50
(RPM).

Troubleshooting LED
Indicators

The RUN, FDBK/U. PWR, and CONFIG INV LED indicators on the SLC
Servo Module serve as diagnostic tools for troubleshooting. Refer to
the table below for general conditions.

General Condition

Potential Cause

Possible Resolution

The RUN LED is not green.

Indicates a major SLC Servo Module malfunction
or lack of power from the backplane or the user
supplies.

1. Check that power is present from the

backplane.

2. If power is present, replace the SLC

Servo Module.

The FDBK/U PWR LED is
red.

No user power.

Check user power supply and connections to
termination panel.

The CONFIG INV LED is
red.

Using default values or invalid data

Check fault word code.

Change parameter.

Reconfigure parameters.