10-2 Troubleshooting

Hardware Setup

Check wiring to diagram, get the FDBK/UPWR light out.

This insures that you have feedback, and all of the required user
power.

1. Do you have 0.00 – 0.80 for off state or 4.75 – 5.25 VDC on the

encoder signals.

2. Are all of the DC commons tied together and to ground as

shown in the manual.

3. Are all of the voltages present 5V, +15V, -15V, 24VDC.

Do a battery box test. (If unable to control drive)

1. This is done by pulling the DRIVE (analog voltage output) plug

on the HT panel.

2. Pull the ENABLE plug, and jump the drive enable signal to the

drive.

3. Tune the Drive without the HSRV, to insure the drive will accept

analog commands.

4. Use a AA 1.5V battery wired between the DRIVE and DR

RET(analog voltage). This should make the motor turn in one
direction, swap the connections on the battery and the motor
should spin in the other direction.

At this point the Drive should be tuned, and have turned in both
directions with the battery box test. And the FDBK/UPWR light
should be off.

Software Setup

Configure the HSRV module

Downloading Your Configuration

When you download your configuration using the M0 file for the
module that you want, the types of data that are included are:

Discrete parameters

Floating-point parameters