Troubleshooting 10-13

2051

No communication with the SLC Servo Module has
occurred within the last 5 seconds. This error causes
Estop.

1. Reset from Estop.
2. If the problem occurs again check the SLC

processor.

Note: Switching from run mode to program mode on the
SLC Servo Module also causes this error to appear.

2052

Set on power-up.

Issue a Clear Fault (O:s.1/8) or a Clear all faults (O:s.1/9)

2053

SLC Servo Module requesting Estop.

Turn discrete Estop request off.

2054

The user power supply is shorted or not connected. This
error causes Estop.

1. Check the user power and its connections to the

SLC Servo Module.

2. After it is fixed, reset from Estop.

2055

The user Estop string has opened.

1. Check that the device that opened the string is

functioning properly.

2. Reset from Estop.

2056

Watchdog disable jumper is installed.

Remove it.

2057

The backplane is disabled.

The SLC Servo Module lost backplane
communications.

I/O reset was detected.

The backplane was disabled.

Major Fault
Message No.

Potential Cause

Possible Resolution