Publication 1746-6.1.2 - July 2000

5-4 Wiring the SLC Servo Module

Figure 5.2 Equivalent Fast Input Circuit

Figure 5.3 Equivalent Fast Output Circuit

Wiring Hardware
Overtravels

Because the system must go into Estop when a hardware overtravel is
tripped, do the following to the hardware overtravel limit switches of
each axis:

Wire them into the customer Estop string.

Position them outside the software overtravels (see Figure 5.4).

+24V DC

47K

W

11K

W

15K

W

Control
Module

Termination
P anel

1746-HCA

Termination
P anel

C ontrol
Module

+5V D C

+24

D C

R et

FO .1

1746-HCA

K2