6-4 Testing Your SLC Servo Module Hardware

4. Short the (machine tool) hardware Estop string.

5. Press and hold down the Estop Reset push-button. The

following events occur:

SLC Servo Module detects an Estop reset request.

SLC Servo Module closes the software-controlled Estop relay
in the SLC Servo Module.

Because the Estop string is shorted, Relay CR1 seals the Estop
Reset push-button.

6. Release the Estop reset push-button. The contacts in the Relay

CR1 remain closed (in the power-on condition).

7. Verify that the Relay CR1 contacts are closed by doing the

following:

Perform a continuity check on one of the drive enable
contacts that are normally open.

Check the Relay CR1 contacts visually to see if they are
closed.

8. Remove the string-out/string-in jumper. Relay CR1 drops out

indicating an Estop condition.

9. Reconnect the Estop string and drive enable to the termination

panel to get the system up and running.

IMPORTANT

Open each contact on the string so that the system
goes into Estop.