Wiring the SLC Servo Module 5-13

Figure 5.10 Wiring a +5V, ±15V, and a +24V Power Supply

Wiring Encoders

When you wire encoders, use a single, continuous, shielded cable
segment. Wire the cable directly from the encoder to the termination
panel.

Cable length depends on the power supply for the user-side. Voltage
at the encoder must be within the voltage requirement limits specified

E X T P O W E R

+5 V

R E T

+1 5 V

- /+R E T

+2 4

+2 4 R E T

E G N D

- 1 5 V

+5V

+5V

+15V

+/- 15V

- 15V

A C H I

A C LO

+24V

+24V R E T

A C Line

+24V P o wer S u p p ly

L1

L2

COMM

COMM

Electrical Cabinet
Ground Bus

14 AWG

14 AWG (3)

14 AWG

14 AWG

ATTENTION

!

To avoid unpredictable operation of your SLC Servo
Module, connect the +5V COMM to the +24V COMM.

If voltage sources are coming from two separate
isolated power supplies, tie the +24V return to the
+5V return.