Wiring the SLC Servo Module 5-5

Software Overtravel Limits

Software overtravel limits appear in the table below.

When you are using a check, the SLC Servo Module tests each
program for motion past an overtravel limit before the programmed
motion is executed.

The SLC Servo Module monitors software overtravel limits
continuously during motion. Software overtravels are disabled during
homing and are not active until the axis is homed. Software overtravel
limits are located inside hardware overtravel limits. Hardware
overtravel limits cause Estop when tripped.

Figure 5.4 Software Overtravel Limits

Connecting Home Limit
Switch as a Fast Input

You can configure the home limit switch to come from the termination
panel, or from the backplane by setting configuration word 1, bit 0.
The 1 represents termination panel Fast Input 3. The 0 represents

Name

What it specifies

Default

Range

Software overtravels used

Whether control checks
software overtravel limits

Yes

Yes (used) or
No (not used)

IMPORTANT

Check positive and negative software and hardware
overtravel limits only if Overtravels Used (word 0, bit
7) is set.

0

-

+

Negative Overtravel Limit
W10-W11

Positive Overtravel Limit
W8-W9

Positive Hardware Overtravel Limit
(causes Estop)

Negative Hardware Overtravel Limit
(causes Estop)