Error messages and diagnosis – Rockwell Automation 1746-HSRV SLC Servo Control Module User Manual User Manual

Page 166

Advertising
background image

Publication 1746-6.1.2 - July 2000

Troubleshooting 10-7

The following table shows the status indicators for the LEDs and what
action might need to be taken.

Error Messages and
Diagnosis

The following tables provide a numerical listing of informational
messages, minor fault messages, and major fault messages
accompanied by potential causes and possible resolutions.

When the LED status indicators
are:

Your system status is:

And the action to take is:

RUN
FDBK/U.PWR
CONFIG INV

On
Off
Off

System O.K.

Continue

RUN
FDBK/U.PWR
CONFIG INV

Off
Off
Off

Power is not applied or there is a
catastrophic
failure.

Apply power

RUN
FDBK/U.PWR
CONFIG INV

Off
Off
On

Hardware failure

1. Troubleshoot

2. Repair the hardware that failed

RUN
FDBK/U.PWR
CONFIG INV

Off
On
Off

Hardware failure

1. Troubleshoot

2. Repair the hardware that failed

RUN
FDBK/U.PWR
CONFIG INV

Off
On
On

Power-up or RAM failure

1. Verify power supply connections for +24,
±15, +5, and encoder feedback signals

2. Troubleshoot

3. Repair power-up problem or contact
Allen-Bradley for RAM failure

RUN
FDBK/U.PWR
CONFIG INV

On
Off
On

Configuration not loaded

1. Check your program configuration

2. Repair your program configuration

RUN
FDBK/U.PWR
CONFIG INV

On
On
Off

Feedback fault (broken wire, quadrature
fault)
or loss of user power

1. Troubleshoot

2. Repair the feedback wire or the reason
for the loss of user power

RUN
FDBK/U.PWR
CONFIG INV

On
On
On

Configuration not loaded and loss of user
power

1. Check your program configuration

2. Repair your program configuration

3. Repair the reason for loss of user power