6 - 18 6 - 18

MELSEC-Q

6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL

(2) Confirmation using the module and GX Configurator-SC

1) Confirmation using the display LED

When the Q series C24 detects an error, including a transmission error, the

ERR LED lights up. (See Chapter 10.)

2) Confirmation using GX Configurator-SC

• The monitor function is used to check for errors. (See Sections 8.6.3 and

8.6.5.)

• The ERR LED is turned off with the ERR LED OFF function. (See Section

8.6.10.)

3) Confirming the error code

Use one of the following to confirm the error code.

• GX Configurator-SC monitor function (See Section 8.6.5.)

• GX Developer buffer memory monitor function (monitors addresses

258

H

/268

H

)

(3) Receive data when a reception error occurs

(a) Storing receive data

The receive data for which an error was detected is discarded and only the

normally received data is stored in the Q series C24.

Thus, there may be missing data among the data that has been read to the

PLC CPU when a reception error occurs.

(b) Reading receive data

When receive data is read to the PLC CPU by turning the reception

abnormal detection signal (X4/XB) ON, the data that was normally received

prior to the error detection is read. Read and discard receive data as

needed.