6 - 22 6 - 22

MELSEC-Q

6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL

6.2 Sending Data to the External Device

This section explains data transmission from the PLC CPU to the external device.

6.2.1 Transmission methods

The following shows how to send data in any format using the non procedure protocol.

Transmission area

(buffer memory)

STX

A

B

C

D

E

F

G

H

ETX

Transmission data

(02

H

) (41

H

)

(48

H

)

(47

H

)

(46

H

)

(45

H

)

(44

H

)

(43

H

)

(42

H

)

(03

H

)

A

(41

H

)

G

(47

H

)

E

(45

H

)

C

(43

H

)

STX

B

D

F

H

(02

H

)

(48

H

)

(46

H

)

(44

H

)

(42

H

)

ETX

(03

H

)

10

(0A

H

)

(00

H

)

3)
Transmission data

PLC CPU

ETX

H

(03

H

)

(48

H

)

(41

H

)

(03

H

)

External device

A

STX

1) 2)
OUTPUT instruction

Q series C24

Transmission
data count
designation
area

Transmission
data
designation
area

OUTPUT instruction
completion device

OUTPUT instruction

OUTPUT

Transmission instruction

Contents

CH1/CH2

Control timing

1) Transmission data is stored in the device designated with the OUTPUT instruction.

2) Control data is stored in the device designated with the OUTPUT instruction.

3) When the OUTPUT instruction is executed, the Q series C24 sends the amount of

data designated by the transmission data count from the transmission data area to

the external device in ascending order of the transmission data area addresses.