Melsec-q, 3 specifications – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 75

Advertising
background image

3 - 25 3 - 25

MELSEC-Q

3 SPECIFICATIONS

Address

Decimal (Hex)

Applicable

protocol

CH1

CH2

Application

Name

Initial
value

MC Non

Bi

Registration

allowed/not

allowed

Reference

section

Transmission sequence status (For confirmation of MC protocol
communication status)

597

(255

H

)

613

(265

H

)

0: Waiting for receiving command
1: Receiving command
2: Command reception complete
3: Waiting to access PLC CPU
4: Accessing PLC CPU
5: PLC CPU access complete
6: Response message transmission

R

On-demand execution result

598

(256

H

)

614

(266

H

)

0 : Normal completion
1 or more: Abnormal completion (error code)

RW

Section

8.6.4

Section

10.1.4

Data transmission result

599

(257

H

)

615

(267

H

)

0 : Normal completion
1 or more: Abnormal completion (error code)

Data reception result

600

(258

H

)

616

(268

H

)

0 : Normal completion
1 or more: Abnormal completion (error code)

0

RW

Not allowed

Chapter 6
Chapter 7

Section

8.6.5

Section

8.6.6

601

(259

H

)

617

(269

H

)

System area

MC protocol transmission error code
(excludes A compatible 1C frame communication)

602

(25A

H

)

618

(26A

H

)

0: No error

1 or more: Transmission error code

RW

Section

8.6.4

Receive user frame (nth)

603

(25B

H

)

619

(26B

H

)

For confirmation
of communica-
tion result

0 : Not received
1 to 4: Combination of user frame No. designations for reception

message

0

R

Not allowed

Section

8.6.5

604 to

607

(25C

H

to 25F

H

)

620 to

1023

(26C

H

to

3FF

H

)

Use prohibited

System area

Transmission data count designation

1024

(400

H

)

2048

(800

H

)

0: No designation

1 or more: Number of send data

Transmission data designation

1025 to

1535

(401

H

to

5FF

H

)

2049 to

2559

(801

H

to

9FF

H

)

Data to be sent to an external device

Receive data count (Number of data for which read is requested)

1536

(600

H

)

2560

(A00

H

)

0: No receive data

1 or more: Number of receive data

Receive data

1537 to

2047

(601

H

to

7FF

H

)

2561 to

3071

(A01

H

to

BFF

H

)

Transmission/rece

ive area

Data received from an external device

0

RW

Not allowed

Chapter 6

Chapter 7

Section

8.4.5

Section

8.4.7

3072 to 6911

(C00

H

to 1AFF

H

)

For user

User free area (3840 words)

Determined by the user.

0

RW

Not allowed

6912to 6952

(1B00

H

to 1B28

H

)

For registration No. 8001

H

6953 to 6993

(1B29

H

to 1B51

H

)

For registration No. 8002

H

6994 to 7034

(1B52

H

to 1B7A

H

)

For registration No. 8003

H

7035 to 7075

(1B7B

H

to 1BA3

H

)

For registration No. 8004

H

7076 to 7116

(1BA4

H

to 1BCC

H

)

For registration No. 8005

H

7117 to 7157

(1BCD

H

to 1BF5

H

)

For registration No. 8006

H

7158 to 7198

(1BF6

H

to 1C1E

H

)

For registration No. 8007

H

7199 to 7239

(1C1F

H

to 1C47

H

)

For registration No. 8008

H

7240 to 7280

(1C48

H

to 1C70

H

)

For registration No. 8009

H

7281 to 7321

(1C71

H

to 1C99

H

)

For registration No. 800A

H

7322 to 7362

(1C9A

H

to 1CC2

H

)

For registration No. 800B

H

7363 to 7403

(1CC3

H

to 1CEB

H

)

For registration No. 800C

H

7404 to 7444

(1CEC

H

to 1D14

H

)

For registration No. 800D

H

7445 to 7485

(1D15

H

to 1D3D

H

)

For registration No. 800E

H

The user registration area has the following combined uses, with

data written by the user according to the purpose of use by the

TO instruction, etc.

See each explanation item concerning the configuration of each

area, the data written, etc.

(1) If data communications is being carried out by user

registration frame.

• User registration frame (User’s Manual (Application),

Chapter 9)

(2) If data communications is being carried out by the modem

function.

• Initialization Data (User’s Manual (Application) Section

3.4.3)

• Connection Data (User’s Manual (Application) Section

3.4.4)

Not allowed

Refer to left

description

Advertising