10 - 16 10 - 16

MELSEC-Q

10 TROUBLESHOOTING

Protocol

Error code

(Hexa-

decimal)

Error

Error Contents

Signal
name

Corrective action

MC

Non

Proce-

dure

Bidire-

ctional

7148

H

Extension R block

No. error

A nonexistent extension file register block No. was

designated.

A block No. being used as an extension comment

area, sampling trace area, or status latch area was

designated.

PRO

Correct the designated block

No. and restart data

communications.

7149

H

System error

The OS of the Q series C24 detected some error.

(

1)

714A

H

Cannot execute a

command during

RUN

A write command was designated when "Disable

write during RUN" was set.

Parameter or sequence program was written during

RUN.

C/N

Change the setting to "Enable

write during RUN" and restart

data communications.

Stop the CPU and restart data

communications.

714B

H

to

714D

H

System error

The OS of the Q series C24 detected some error.

(

1)

714E

H

Monitor network

No. error

The written monitor network No. and the monitor

request network No. are different.

C/N

Check and correct the other

station access valid module No.

in the network parameters.

Rewrite the monitor data.

7150

H

System error

The OS of the Q series C24 detected some error.

(

1)

7151

H

PLC No.

designation error

A PLC No. other than "FF" or "0 to 64(00

H

to 40

H

)"

was designated.

C/N

Check and correct the external

device transmit message and

restart data communications.

7152

H

System error

The OS of the Q series C24 detected some error.

(

1)

7153

H

Frame length error

The received message length has exceeded the

allowable range.

CHn

ERR.

Review the transmission

message.

Correct the message format so

the number of access points is

within the allowable range.

7154

H

System error

The OS of the Q series C24 detected some error.

(

1)

7155

H

Unwritten monitor

data error

Monitoring was requested before monitor data was

written.

PRO

Write the device to be monitored

before issuing a monitor

request.

7156

H

System error

The OS of the Q series C24 detected some error.

(

1)

7160

H

PLC access error

CPU model name cannot be confirmed.

C/N

If there is an error in the CPU,

remove the CPU error and

restart data communications.

7161

H

to

7163

H

System error

The OS of the Q series C24 detected some error.

(

1)

7164

H

Request error

Either the request or the device designation method

is wrong.

Check the transmission

message/request from the

external device, make the

necessary corrections, and send

again.

7166

H

System error

The OS of the Q series C24 detected some error.

(

1)

7167

H

A write command was designated when "Disable

write during RUN" was set.

C/N

Change the setting to "Enable

write during RUN" and restart

data communications.

7168

H

Cannot execute a

command during

RUN

A command that cannot be executed during RUN

was designated.

C/N

Stop the CPU and restart data

communications.

7169

H

CPU error

Cannot communicate normally with the CPU.

C/N

If there is an error in the CPU,

remove the CPU error and

restart data communications.

716A

H

to

716C

H

System error

The OS of the Q series C24 detected some error.

(

1)

716D

H

Monitor data was not written using QnA compatible

2C/3C/4C frame.

PRO

716E

H

Monitor data write

error

Monitor data was not written using A compatible 1C

frame.

PRO

Rewrite monitor data.