Melsec-q, 1) err. led on factors, Point – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 257

Advertising
background image

10 - 6 10 - 6

MELSEC-Q

10 TROUBLESHOOTING

10.1.2 Initializing error information of the serial communication module

This section explains the ERR. LED ON factors and the error code initialization (clear)

for the Q series C24.

(1) ERR. LED ON factors

When any of the following errors occurs, its error code is stored in the buffer

memory corresponding to the interface (CH) where the error occurred, and the

ERR. LED turns on.

Error code storage buffer memory

Applicable protocol

Address

Cause of error

CH1

CH2

Name

MC

Non-

procedure

protocol

Bidirec-

tional

protocol

Switch setting error

Mode switching error

203

H

Switch setting error, mode switching error

storage area

On-demand execution

error

256

H

266

H

On-demand execution result storage area

Data transmission error

257

H

267

H

Data transmission result storage area

Data reception error

258

H

268

H

Data reception result storage area

MC protocol transmission

error

025A

H

026A

H

MC protocol transmission error code

Monitoring device error

2205

H

2305

H

PLC CPU monitoring function execution

result

(2) Turning off the ERR. LED and initializing the error codes by GX

Configurator-SC (Refer to Section 8.6.10)

(a) When turning off the ERR. LED and initializing the error codes

By making the CH ERR. clear request on the "Monitor/Test" screen, the

ERR. LED of the Q series C24 turns off and the stored error codes are

initialized.

(b) When initializing the communication error information

By making the Communication error clear request for CH and to turn LED

off on the "Monitor/test others" screen, the LEDs (ERR., NEU.) of the Q

series C24 turn off and the communication error information is initialized.

(3) Turning off the ERR. LED and initializing the error codes by

sequence program

(a) Input signals used to notify of error occurrences and output signals used to

initialize the error code

I/O signal

Name of status information

Description/function

XE

Error occurrence on CH1 side

Turns on upon error occurrence in CH1 interface.

Input signal

XF

Error occurrence on CH2 side

Turns on upon error occurrence in CH2 interface.

YE

CH1 Error information initialization request

Turns on when initializing error code of interface on CH1 side.

Output signal

YF

CH2 Error information initialization request

Turns on when initializing error code of interface on CH2 side.

Initialization of error code is continuously performed when output signal (YE/YF) is

on.

POINT

The CHn side error information can be initialized by an off request to the LED off

request area (address 1

H

) of the buffer memory. By using output signals YE to YF,

the error codes stored in the above buffer memory can further be initialized

(cleared).

Advertising
This manual is related to the following products: