Melsec-q, Point – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 88

Advertising
background image

4 - 7 4 - 7

MELSEC-Q

4 SETTINGS AND PROCEDURES PRIOR TO OPERATION

(2) Connection examples

(a) Connection example with an external device capable of turning on and off the

CD signal (No. 1 pin)

Q series C24

Pin No.

CD

RD(RXD)

SG

DSR(DR)

1

2

3

4

5

6

7

8

9

External device

Signal name

Signal name

SD(TXD)

DTR(ER)

RS(RTS)

CS(CTS)

RI(CI)

CD

RD(RXD)

SG

DSR(DR)

SD(TXD)

DTR(ER)

RS(RTS)

CS(CTS)

The CD terminal check setting is set according to the specification of the external

device. When wiring shown above, DTR/DSR control or DC code control may be

performed.

(b) Connection example with an external device not capable of turning on and off

the CD signal (No. 1 pin)

1) Connection example 1

Q series C24

Pin No.

CD

RD(RXD)

SG

DSR(DR)

1

2

3

4

5

6

7

8

9

External device

Signal name

Signal name

SD(TXD)

DTR(ER)

RS(RTS)

CS(CTS)

RI(CI)

CD

RD(RXD)

SG

DSR(DR)

SD(TXD)

DTR(ER)

RS(RTS)

CS(CTS)

When wiring shown above, DTR/DSR control or DC code control may be performed.

2) Connection example 2

Q series C24

Pin No.

CD

RD(RXD)

SG

DSR(DR)

1

2

3

4

5

6

7

8

9

External device

Signal name

Signal name

SD(TXD)

DTR(ER)

RS(RTS)

CS(CTS)

RI(CI)

CD

RD(RXD)

SG

DSR(DR)

SD(TXD)

DTR(ER)

RS(RTS)

CS(CTS)

When wiring shown above, DC code control may be performed.

POINT

If the PLC CPU and an external device cannot be communicated, try to perform data

communication as a connection test, using the wiring connection as shown in

Connection example 2.

If data can be communicated using the wiring connection shown in Connection

example 2, rewire after checking the interface specifications on the external device

side.