Melsec-q, 3 specifications – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 72

Advertising
background image

3 - 22 3 - 22

MELSEC-Q

3 SPECIFICATIONS

Address

Decimal (Hex)

Applicable

protocol

CH1

CH2

Application

Name

Initial

value

MC Non

Bi

Registration

allowed/not

allowed

Reference

section

User frame being transmitted

182

(B6

H

)

342

(156

H

)

User frame being
transmitted

0 : Not send
1 to 100: User frame being transmitted (nth)

0

R

Not allowed

CR/LF output designation

183

(B7

H

)

343

(157

H

)

0: Do not send.

1: Send.

Output head pointer designation

184

(B8

H

)

344

(158

H

)

0: No designation

1 to 100: Send from nth

Output count designation

185

(B9

H

)

345

(159

H

)

0: No designation

1 to 100: Output n

186 to

285

(BA

H

to

11D

H

)

346 to

445

(15A

H

to

1BD

H

)

For user frame
being transmitted
designation

Output frame No. designation (A maximum of 100 can be specified)

0

RW

Allowed

Section

8.4.7

Chapters 9

and 11 of

User's

Manual

(Application)

Message wait time designation

286

(11E

H

)

446

(1BE

H

)

For designation
of transmission
wait time

0: No wait time

1

H

to F

H

: Wait time (unit: 10 ms)

RW

Section

8.4.6

Transmission transparent code designation 1st

0000

H

: No designation

Other than 0000

H

: Designated (below)

287

(11F

H

)

447

(1BF

H

)

• Transparent code (b0 to b7)

00

H

to FF

H

: Transparent code

• Additional code (b8 to b15)

00

H

to FF

H

: Additional code

Receive transparent code designation

0000

H

: No designation

Other than 0000

H

: Designated (below)

288

(120

H

)

448

(1C0

H

)

For designation

of transparent

code

• Transparent code (b0 to b7)

00

H

to FF

H

: Transparent code

• Additional code (b8 to b15)

00

H

to FF

H

: Additional code

ASCII-BIN conversion designation

289

(121

H

)

449

(1C1

H

)

For conversion
designation

0: No conversion

1: Convert

0

RW

Allowed

Section

8.4.5

Chapter 12

of User's

Manual

(Application)

290 to

303

(122

H

to

12F

H

)

450 to

511

(1C2

H

to

1EF

H

)

Use prohibited

System area

512

(200

H

)

For confirmation
of station No.
setting status

Station No. (switch setting)

Depends

on

parame-

ter setting

LED ON status and communication error status on CH1 side

0: Turned off/OFF, no error

1: Turned on/ON, error

513

(201

H

)

SD WAIT (b0)

SIO (b1)

PRO. (b2)

P/S (b3)

For system (b8) to (b15)

C/N (b4)

NAK (b5)

ACK. (b6)

NEU. (b7)

LED ON status and communication error status on CH2 side

0: Turned off/OFF, no error

1: Turned on/ON, error

514

(202

H

)

For confirmation

of LED ON status

and

communication

error status

SD WAIT (b0)

SIO (b1)

PRO. (b2)

P/S (b3)

C/N (b4)

For system (b8) to (b13)

NAK (b5)

ACK. (b6)

NEU. (b7)

CH2.ERR. (b14)

CH1 ERR. (b15)

Depends

on

module

status

R

Not allowed

Section 4.3

Section

4.5.2

Section

8.6.9

Advertising