Appendix 9.12 When changing the communication protocol and transmission setting

This section provides a program example that changes the communication protocol

and transmission setting using the REMFR/REMTO instructions and I/O signals.

(When the module is used on a MELSECNET/H remote I/O station, the station No.

cannot be changed because the UINI instruction is unavailable.)

For changing the communication protocol and transmission setting, refer to Chapter 15

of the User's Manual (Application).

(1) Program conditions

When the change command (X1031) turns on, the communication protocol and

transmission setting are changed.

(a) Devices used by user

• Change command .................................................................. X1031
• Changing flag .......................................................................... M300
• Change completion flag .......................................................... M301
• CH1 change command pulse signal ...................................... M10
• CH1 change command........................................................... M11
• CH1 mode switching completion............................................ M12
• CH1 receive processing.......................................................... M13
• CH1 send processing ............................................................. M14
• CH2 change command pulse signal ...................................... M20
• CH2 change command........................................................... M21
• CH2 mode switching completion............................................ M22
• CH2 receive processing.......................................................... M23
• CH2 send processing ............................................................. M24
• REMFR/REMTO instruction completion device..................... M100 to 107
• REMFR/REMTO instruction abnormal completion flag......... M200 to 205
• Switching mode No. designation............................................ D0, D10
• Transmission specifications after switching designation ....... D1, D11
• Switch setting error and mode switching error status............ D2, D12

(b) Buffer memory settings used in this example

Address, Decimal

(Hexadecimal)

Bit

CH1

CH2

Position

Specified

value

Description

Set value

114 (90

H

)

304 (130

H

)

Switching mode No. designation

MC protocol

(Format 1)

0001

H

b0

OFF

Operation

setting

Independent

b1

OFF

Data bit

7 bits

b2

OFF

Parity bit

No

b3

OFF

Even/odd parity

Odd

b4

ON

Stop bit

2 bits

b5

ON

Sum check

code

Yes

b6

OFF

Write during

RUN

Prohibited

b7

ON

Setting

modifications

Allowed

b8 to b11

Communication

rate setting

9600bps

B12 to 14

All OFF

For system

145 (91

H

)

305 (131

H

)

B15

ON

Transmission
specifications

after switching

designation

Transmission
specifications

after switching

designation

Make setting

as set in this

area.

85B0

H

515 (203

H

)

Switch setting error and mode switching error status