Melsec-q, 10 troubleshooting – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 268

Advertising
background image

10 - 17 10 - 17

MELSEC-Q

10 TROUBLESHOOTING

Protocol

Error code

(Hexa-

decimal)

Error

Error Contents

Signal
name

Corrective action

MC

Non

Proce-

dure

Bidire-
ctional

716F

H

Device error

A nonexistent device was designated.

Device that cannot be specified by the

corresponding command was designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

7170

H

Number of access points exceeded the range.

PRO

7171

H

A device that cannot be designated was designated.

PRO

7172

H

A compatible 1C
frame error

Written number of monitoring points is incorrect. For

example, [0] was designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

7173

H

Monitor data write
error

Monitor data was written for a CPU other than a

Q/QnACPU using QnA compatible 2C/3C/4C frame.

PRO

Write the monitor data and use

the A compatible 1C frame to a
CPU other than a Q/QnACPU.

7E00

H

to

7E05

H

System error

The OS of the Q series C24 detected some error.

(

1)

7E06

H

Buffer memory
address setting
error

Transmit/receive buffer memory addresses are in

the special applications area.

Change the buffer memory

addresses so that they are outside
the special applications area.

7E07

H

to

7E0A

H

System error

The OS of the Q series C24 detected some error.

(

1)

7E40

H

Command error

A nonexistent command or subcommand was

designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

7E41

H

Data length error

A data length exceeding the number of points that

can communicate during random read/write was
designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

7E42

H

Error count error

Number of requested points exceeds the range for

the command.

PRO

Check and correct the external

device transmit message and
restart data communications.

7E43

H

Device error

A nonexistent device was designated.

Device that cannot be specified by the

corresponding command was designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

7E44

H

Timer 1 time-out
error

A response message was not returned within the

response monitoring time (timer 1) monitoring time.

C/N

Make the timer 1 monitoring

time longer.

When accessing another

station's CPU, check if the
routing parameters match.

7E46

H

System error

The OS of the Q series C24 detected some error.

(

1)

7E47

H

Continuous request
error

The next request was received before a response

message was returned for the preceding request.

PRO

Do not issue continuous

requests from the external
device.

Set the timer 1 monitoring time

to the external device time-out
time.

7E48

H

to

7E4C

H

System error

The OS of the Q series C24 detected some error.

(

1)

7E4D

H

Error during data
transmission

Mode switching was executed during data

transmission.

CHn

ERR.

Make arrangements between

the target device and PLC CPU
so that mode switching is not
executed during data
transmission.

7E4E

H

System error

The OS of the Q series C24 detected some error.

(

1)

7E4F

H

Device point count
error

Access point count is incorrect.

PRO

Check and correct the external

device transmit message and
restart data communications.

7E50

H

User frame No.
designation error

A user frame No. outside the range was designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

Recheck the frame No..

7E51

H

Unwritten user
frame error

An unwritten user frame No. was designated.

PRO

Write the frame beforehand.

Change the frame No. and

restart data communications.

Recheck the frame No..