10 - 35 10 - 35

MELSEC-Q

10 TROUBLESHOOTING

10.3.8 Troubleshooting when communication error "PRO." generates

Symptom

Cause

Corrective action

MC

B

id

ir

e

ct

io

nal

No

n

procedure

• Communications were

performed with a control
procedure different from
the Q series C24
communication protocol
setting.

• Some of the data are

different from the control
procedure.

• Designated command

does not exist.

• The device No.

designation is not the
character count
corresponding to the
command.

• Check the Q series C24 communication

protocol setting and the message from the

external device and match the settings, or

correct the message and restart data

communications.

• The characters in the

message include a data
other than the "A to Z",
"0 to 9", "

", and

control data.

• Check and correct the external device message

and restart data communications.

Note

• Only the data "0 to 9" and "A to F" can be

handled as character area data during
communications using an MC protocol (ASCII
mode). Therefore, when transmitting a
character string as data, convert the ASCII code
of each character string to 2-byte binary code.

Examples)

• Transmitting the character "G"

The ASCII code for the character "G" is 47

H

and is transmitted as the two bytes 34

H

, 37

H

.

• Transmitting the character "A"

The ASCII code for "A" is 41

H

and is

transmitted as the two bytes 34

H

, 31

H

.

If the ASCII code 41

H

for the character "A" is

transmitted unchanged, the Q series C24
ASCII-BIN conversion will convert it to A

H

(10) and pass it to the PLC CPU.

• A device No. outside the

designated range was
designated.

• When designating a device, check "Device

setting" of the parameters written to the CPU
and correct it to a device No. within the
designated range and restart data
communications.

• Communication error

signal "PRO" turned on.

• A remote RUN/STOP

request was issued
while remote STOP was
applied from another
module.

• Check if remote STOP is applied from another

module and restart data communications.