2 sending data to the external device, 1 transmission methods, Melsec-q – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 166

Advertising
background image

7 - 15 7 - 15

MELSEC-Q

7 DATA COMMUNICATIONS USING BIDIRECTIONAL PROTOCOL

7.2 Sending Data to the External Device

This section explains data transmission from the PLC CPU to the external device.

7.2.1 Transmission methods

The following shows the method of sending data to the external device through data

communication using the bidirectional protocol.

PLC CPU

PLC program

Buffer memory

Transmission area

Transmission
completed

1)
Write
(BIDOUT
instruction)

External

device

(00

H

to FF

H

)

4)

(When abnormal)

2)

(When normal)

(00

H

to FF

H

)

Any data

3)

5)

Data

Q series C24

Sum check code Data portion

Data length ENQ

ACK

NAK

Error code

BIDOUT instruction
completion device

BIDOUT instruction

CH1/CH2

Control timing

Send instruction

Contents

BIDOUT

1) Data such as control data and transmission data are stored in the device designated

with the BIDOUT instruction and then the BIDOUT instruction is executed.

2) The transmission data count and transmission data are written into the

transmission area of the buffer memory.

3) The Q series C24 sends data by adding the control code ENQ at the beginning of

the data.

When "Sum check" is designated with GX Developer, the Q series C24 adds

the sum check code calculated by internal processing to the end of the
message and then transmits the message.
When "No sum check" is designated with GX Developer, no sum check code is
sent.

4) A response for the data transmission (for normal completion: ACK message; for

abnormal completion: NAK message) is received.

5) The execution of the BIDOUT instruction completes with the transmission

processing completion of the Q series C24.

Advertising