background image

10 - 30 10 - 30

MELSEC-Q

10 TROUBLESHOOTING

10.3.2 Troubleshooting when "RD" LED does not blink even though an external device is

transmitting a message

Symptom

Cause

Corrective action

MC

Bidi

rec

tio

nal

No

n

procedure

• Signal lines are not

connected correctly.

• Check if the Q series C24 and external RD and

SD signal lines are cross connected.

• Use the external device OPEN statement to

check if the opened port and the cable

connection port are matched.

• External device

transmission control

signals are not turned

ON.

• Connect the wiring so that the "DSR", "CS", and

other transmission control signals are ready.

Note

• Since the control signal specifications depend

on the device, connect the wiring by seeing

the instruction manual of the device used.

• "RD" does not blink

even through an

external device is

transmitting a message.

• If the message passes

through an RS-232

RS-422 converter,

modem, etc., the signal

is interrupted at one of

the intervening devices.

• Check the specifications of the converter and

modem and recheck the settings and wiring

Advertising
This manual is related to the following products: