10 TROUBLESHOOTING

10.3.13 Troubleshooting when it is unclear whether the communication error cause is in the

Q series C24 or an external device

Symptom

Cause

Corrective action

MC

B

id

ir

e

ct

io

nal

No

n

procedure

• Whether the

communications error

cause is in the Q series

C24 or an external

device is unclear.

• Test the Q series C24 as described below to

check where the cause is.

1) Check the hardware.

• The Q series C24 must be installed firmly.

• The pins of the Q series C24 must not be

bent or otherwise abnormal.

2) Test the Q series C24 alone. (See Section

4.7.)

• ROM/RAM/switch test must not generate

any errors.

• Self loopback test must not generate any

errors.

3) Check the state of the PLC CPU.

• There must not be any errors that stop

PLC CPU operation.

Note

• The following methods are available for

testing if normal communications are possible
with the Q series C24 alone.

1) With one the Q series C24, set CH1 and

CH2 to the non procedure protocol and
connect the wiring the same as for the self
loopback test and transmit data from one
channel and receive the transmitted data
at the other channel. If the transmitted
data and the received data are the same,
transmit and receive processing is
performed normally.

2) When two Q series C24 are available, set

one Q series C24 to the non procedure
protocol and the other Q series C24 to a
dedicated protocol and transmit an MC
protocol message from the non procedure
protocol station. If the MC protocol station
returns the transmit message normally,
transmit and receive processing is
normal.