10 TROUBLESHOOTING

10.3.14 Troubleshooting when data cannot be communicated via modem

Symptom

Cause

Corrective action

MC

Non

procedure

protocol

Bidirection

al protocol

• A modem initialization error occurs.

• Check the error code and execute

processing accordingly.

• Modem connection channel designation is

not performed.

• Set Modem connection channel

designation.

• Auto modem initialization

cannot be executed.

• There is an error in the switch settings in the

GX Developer.

• Review the switch settings. Set it to match

the local station modem and the TA.

• Communication protocol setting is incorrect.

• Set the communication protocol to MC

protocol, format 5.

• Transmission setting does not match the

external device.

• Review the transmission setting.

• Data cannot be

communicated with GX

Developer supporting the Q

series C24.

• Communication rate does not match the

external device.

• Review the communication rate setting.

• The product is not supported by the GX

Developer.

• Confirm the GX Developer’s S/W version.

• There was an error in the GX Developer

connection system.

• Check the GX Developer’s connection

system.

• Set the connection system on “callback

reception waiting” and connect.

• The GX Developer does not

receive the callback signals

from the Q Series C24.

• There is an error in the GX Developer side’s

modem settings.

• Set the modem’s settings on "Auto

Reception."

• There s an error in the GX Developer’s

connection system.

• Check the GX Developer’s connection

system.

• Correct the Q Series C24’s settings.

• Callback connections from

the GX Developer are

refused by the Q Series

C24.

• There is an error in the connection system’s

telephone No.

• Check the telephone No.

• Change the telephone No. to the data for

callback.

• There is an error in the Q Series C24

setting value.

• Set the callback function designation on the

setting 1 to 3.

• There is an error in the GX Developer’s

connection system.

• Check the GX Developer’s connection

system.

• Check the Q Series C24’s settings.

• When performing Auto

(callback: during fixed/

during designated number)

from the GX Developer,

connection to the Q Series

C24 is refused.

• There is an error in the telephone No. of the

connection system.

• Check the telephone No.

• Change the telephone No. to the data for

callback.

• The timer value for the status of the modem

used or the line is short.

• Adjust each of the timer values for the

callback function on the GX Developer side.

(Line callback cancel wait time, callback

delay time)

• It is possible to connect

from the GX Developer, but

callback from the Q Series

C24 cannot be performed.

• There is a problem with the modem

specifications or settings.

• Check the modem’s specifications and

settings.