4.4.2 Connecting the RS-422/485 interface

The following shows the connection precautions and connection examples when using

the Q series C24 RS-422/485 interface.

(1) Connection precautions

(a) When connecting the Q series C24 SG and FG signals to the external

device, connect them according to the specifications of the external device.

(b) Connect the shield of the connection cable to the FG terminal on either of

the connected devices.

If normal data communication is not obtained due to external noise even if

wiring is made as shown above, perform wiring as follows:

1) Connect between the FG of both stations with the shield of the

connection cable.

On the external device side, however, follow the instruction manual of

the external device.

Be sure to use the plate terminals included with the product when

connecting the braided shield wire to the QJ71C24N-R4.

2) Connect the (FG) of the Q series C24 side to the FG terminal at the power

supply module of the station which has the Q series C24 is installed, or to

the FG terminal of the control panel on which the Q series C24 PLC is

installed.

3) Connect nnA and nnB of each signal in the connection cable as a pair.

Correspondance of the RS-422/485 terminal block and signal location.

Shield

Q series C24

External device

SDA

SDB

RDA

RDB

SG

(FG)

(FG)

SDA

SDB

RDA

RDB

SG

FG

SG

FG

FG

SDA

SDB

RDB

RDA